This product is not currently available. For more information, including distributor inventory, please contact us.

Overview

The PHVS is designed such that it is compatible with polymeric insulated cables independent of the manufacturer and can be adapted with respect to grounding required for various cable constructions. The complete system is separated into the epoxy insulator part and the plug-in part using the pre-moulded silicone stress cone.

The insulators are designed and tested according to IEC 62271-209 and IEC 62271-203. Hence, the PHVS is suitable for all GIS complying with the above standard. Each individual insulator is hermetically sealed and tested. To ensure compatibility with dimensions of oil filled switchgear according to IEC 60859, which require a longer construction length, the entire set up is made available with adaptors. The epoxy insulator can be installed directly at the GIS manufacturer, saving installation time on-site and reducing the risk of contamination of the cable entry housing.

The plug-in part consists of the pre-moulded silicone body for stress control and a mechanical cable lug for easy installation. The plug can be easily separated and re-installed for maintenance purpose. Accessories and add-on kits can be provided for testing and maintenance.

KEY FEATURES

  • Dry interfaces, no oil-filling
  • Insulator complies with IEC 62271-209 and IEC 62271-203
  • Pressure-tight resin housing
  • Pre-fabricated and factorytested silicone-rubber stress cone
  • Torque-controlled multi-contact conductor bolt
  • No special tools required to install the termination
  • Insulated cable gland for sectionalization
  • Type tested according toIEC 60840 and IEC 62067

Features

Please review product documents or contact us for the latest agency approval information.  

Product Type Features

  • Technology  Cold Applied

  • Cable Shield Style  Adaptable

  • Insulation  Polymeric

  • Mechanical Connectors Included  Yes

  • Mechanical Lug Included (Shield)  No

  • Compression Lug Included (Conductor)  No

  • Shelf Life  2 Years

  • Product Family  748

  • Compression Lug Included (Shield)  No

Configuration Features

  • Number of Cores  1

Electrical Characteristics

  • Voltage Class (kV) ≤ 145, ≤ 170, ≤ 245, ≤ 72

Housing Features

  • Armoring  Adaptable

Dimensions

  • Cross-Section Range (mm²) 95 – 2500, 300 – 2500

  • Insulation Diameter (mm) 34 - 108, 34 - 78, 77 – 119

  • Sheath Outside Diameter (mm) 0 – 120, 0 – 135, 0 – 150

Operation/Application

  • Application Type  Indoor

Industry Standards

  • Design Specification  IEC 60840, IEC 62067

Product Availability

  • Product Availability  Worldwide

  • Minimum Order Quantity  1

Packaging Features

  • Minimum Packaging Unit  1

Related Materials

Datasheets & Catalog Pages

Terms and Conditions

Please carefully read the disclaimer before using any of this data. Your use of this data constitutes your acceptance of the terms and conditions set forth below. If you do not agree to those terms and conditions, please click on the I Disagree link.

Disclaimer:
This information has been provided to your free of charge for your use but remains the sole property of TE Connectivity Corporation (''TE'') or SnapEDA,  Inc. or Ultra Librarian/EMA Design Automation, Inc. (collectively, "Company"). While Company has used reasonable efforts to ensure its accuracy, Company does not guarantee that it is error-free, not makes any other representation, warranty, or guarantee that the information is completely accurate or up-to-date. In many cases, the CAD data has been simplified to remove proprietary detail while maintaining critical interface geometric detail for use by customers. Company expressly disclaims all implied warranties regarding this information, including but not limited to any implied warranties or merchantability or fitness for a particular purpose.